Input: No-voltage make contact input, open voltage: 3.3 V DC, short-circuit current: 1 mA or less
(1) Speaker line initial setting activation signal
(2) Speaker line surveillance activation signal
Output: Open collector output, withstand voltage: 30 V DC, control current: 10 mA or less
(1) Monitoring short or open of individual speaker line (zone 1 - 5)
(2) Ground fault (insulation resistance: 50 kΩ or less)
(3) Power amplifier failures
Input/Output
Input: No-voltage make contact input, open voltage: 24 V DC, short-circuit current: 60 mA or less
Output: Open collector output, withstand voltage: 24 V DC (used with VM 24V DC output), control current: 20 mA or less
(1) Speaker Zone information/selection
(2) Power amplifier fault link
Connector: D-sub connector (25-pin, female)
Failure Detection
Power amplifier failure: 20 kHz pilot tone detection
Speaker line failure: 40 Hz impedance detection (Detectable minimu load: 5 W)
Speaker Line Surveillance
Speaker lines are automatically monitored at set time intervals