Skip to main content

VX-2000DS

  • Emergency Power Supply
Emergency Power Supply
VX-2000DS_Angle.jpg
VX-2000DS_Rear.jpg

Emergency Power Supply

Discontinued

VX-2000DS

The VX-2000DS Emergency Power Supply Unit supplies the DC power to each equipment in the VX-2000 system by connecting the VX-200PS Power Supply Unit. It keeps the battery unit that contains 2 x 12 V sealed lead batteries charged compensating for the temperature of the battery charging voltage. When the DC power supply from the VX-200PS stops, the VX-2000DS is automatically switched to the backup battery.

  • Supplies the DC power to each component in the VX-2000 system by means of the VX 200PS Power Supply Unit
  • Keeps the batteries charged
  • Ambient temperature controlled charging voltage
  • Matching battery: 2 x 12 V sealed lead batteries
  • Automatically switch-over in case of AC mains failure
  • EN 54-4 certified, Certificate No: 1134-CPR-083
▼
Power Source
230 V AC, 50/60 Hz
Power Consumption
240 W max.
DC Power Output (AC mode)
6 (25 A max. each), M4 screw terminal, distance between barriers: 11 mm (0.43")
Current Specification
Maximum output current draw from the battery: 43.5 A
Rated maximum continuous output current, I max a: 43.5 A
Rated maximum short duration output current, I max b: 43.5 A
Rated minimum output current, I min: 0 A
Compatible Battery
Yuasa: NPL65-12I (65 Ah)
Charging Method
Trickle charging
Charging Current
5 A max.
Charging Output Voltage
27.3 V ±0.3 V (at 25 °C or 77 °F)
Temperature correction coefficient: –40 mV/°C
Power Supply Input
6, M4 screw terminal, distance between barriers: 11mm (0.43")
Control Connector
RJ45 female connector for connecting the VM-3240VA or VM-3360VA
Twisted-pair straight cable (TIA/EIA-568A standard)
Type of control signal: Battery check, AC power status, DC power status, charging circuit failure, and battery failure
Battery Connection
1 pair of positive and negative terminals
Applicable cable diameter: AWG 6 – AWG 0 (1/0) (Line resistance within 4 mΩ/total)
Cross sectional area: 16 - 50 mm2
Operating Temperature
0 °C to +40 °C (32 °F to +104 °F)
Finish
Panel: Surface-treated steel plate, black, 30% gloss, paint
Dimensions
82 (W) x 88.4 (H) x 377.6 (D) mm (18.98" x 3.5" x 13.29")
Weight
10.5kg (23.15 lb)
Included Accessories
Rack mounting screw x 4, Fiber washer x 4, Blade fuse (40 A) x 3, Fuse (T3.15 A L) x 1, Power Cord (2 m (6.56 ft) x 1, Insulating sheet x 1, Attention label (German) x 1, Fastener hook x 4, Fastener loop x 4, Sticker (Declaration of compliance) x 1, Thermal insulating sheet x 1
Fuse Rating
Blade fuse (40 A), Blade fuse (7.5 A), fuse (T3.15A)
Internal Resistance
Maximum internal resistance of the battery and its associatetd circuitry, Ri max. 50 mΩ
Cable Requirements
Recommended cable parameter for DS-SF Link:
Twisted-pair straight cable (TIA/EIA-568A standard)

Please download Datasheet to access full specifications.

Please sign in to access further technical materials such as software, firmware or EASE files.

  • VX-2000DS_Front.jpg
  • VX-2000DS_Angle.jpg
  • VX-2000DS_Rear.jpg
VX-2000DS_Front.jpg

sns share

close

  • facebook