SX-2000AO

The SX-2000AO is an audio output of the matrix system and can be mounted in an EIA equipment rack (2U size). Multiple units can be decentralized in a whole system. It is equipped with eight audio outputs, and two inputs can be mixed and output. It is also equipped with eight control inputs, and eight control outputs. The SX-2000AO receives audio signals from the audio input unit via digital transmission, but an analog audio input function (1 channel) enables simultaneous all-zone calls for use in emergency situations. Audio output levels are indicated on the level meters provided for each output channel. Volumes can be adjusted for each channel using the volume controls on the front panel or the SX-2000 software. The volume controls can be locked. Any output channel can be monitored using the internal speaker. One control IN/OUT interface allows the number of control inputs and outputs to be increased. It is equipped with an emergency audio input and a 24 V emergency cutoff input. The SX-2000AO has two power inputs and can support a dual-redundant power supply system.

  • Units can be operated in a decentralized system
  • 8 audio outputs and 2 inputs, can be mixed
  • 8 control inputs and 8 control outputs
  • Receives audio signals from the Audio Input Unit via digital transmission
  • Analog audio input function (1 channel) enables simultaneous all-zone calls for use in emergency situations
  • Audio output levels (post-fader levels) indicated on the level meters separate for each output channel
  • Volumes adjustable for each channel by front volume controls or the SX-2000 software
  • The volume controls can be locked by SX-2000 software
  • Any output channel can be monitored using the internal speaker
  • Emergency audio input and 24 V emergency cut-off input
  • 2 power inputs for dual-redundant power supply system
QTY
▼
Power Source
Usable power supply unit: VX-200PS
24 V DC (operational range: 20 V – 40 V DC)
Two power inputs construction enables redundant power supply.
Current Consumption
Under 1.2 A (maximum value in the power operating range)
Under 0.79 A (when operated on 24 V DC)
Note: Excludes current consumption of the external equipment powered by the unit.
Indication
18 alphanumeric characters, Level indication (8 outputs, monitor),
Run indicator, Power indicator, Standby indicator, CPU OFF indicator
Operation
Function keys, Output volume controls, Monitor volume control,
Channel keys, Monitor ON/OFF key, Menu screen operation keys
Audio Output
8 outputs, 0 dB*, suitable load: 600 Ω or above, electronically-balanced output
(changeable into transformer-balanced output), removable terminal
block (12 pins), monitoring possible using built-in speaker
Audio Output Characteristic
Frequency response: 20 Hz – 20 kHz
Sampling frequency: 48 kHz
D/A converter: 24 bit
Control Input
8 inputs, no-voltage make contact input, open voltage: Under 40 V DC,
short-circuit current: 2 mA, photo coupler input,
removable terminal block (6 pins)
Control Output
8 outputs, C contact, no-voltage make contact output: relay contact output
(withstand voltage: 40 V DC, control current: 2 – 300 mA),
removable terminal block (6 pins)
Emergency Line Input
1 input (H, C, E), signals switched by relay, removable terminal block (3 pins),
Emergency audio input is output from all audio output terminals when the
power or a 24 V emergency cutoff input is cut off.
Emergency-Cutoff 24V Input
1 input, input current: under 5 mA, removable terminal block (2 pins),disabled using DIP switch
SX Link
Network I/F
2 100BASE-TX circuits, RJ45 connector, decentralized installation possible
Connection Cable/Device
Shielded Category 5 twisted pair cable for LAN (CAT5-STP)
To be connected via the switching hub specified by TOA.
Note: This network must be made completely independent from other LAN.
Maximum Cable Length
800 m
Analog Link
Input/Output Connector
Input: 1 input, RJ45 connector
Output: 1 output, RJ45 connector
DS Link
Connector/Cable
Shielded Category 5 twisted pair cable for LAN (CAT5-STP)
(each one pair of audio wire, CPU OFF, control wire for system reset/start,and connection check wire)
Operating Temperature
0°C to 40°C
Operating Humidity
35% to 80% RH (no condensation)
Finish
Panel: Aluminum, black, alumite
Case: Surface-treated steel plate
Dimensions
482 (w) x 88.4 (h) x 349 (d) mm
Weight
6.2 kg

Please download Datasheet to access full specifications.

Fully digital audio output unit for installation in 19-inch cabinet racks (IEC 60297) with 8 balanced audio outputs, optionally easily retrofitted transformer.
Two network connections (100BaseTX) for redundant network for audio and control signals, additional analog reserve way.
Redundant power supply for reliable power supply.
8 Control inputs with opto-couplers and 8 control outputs with relay contact, normally closed or normally open free choice, via detachable connectors.
Large multicolored display on the front of the machine for:
-18-digit text display for system information
-Modulation bar indicator for each of the 8 channels
-Status of each channel (on/off)
-Communication error of the network channels
-Collective fault signal
-Emergency mode
Buttons to select of the display of the system information. Separate display for power supply, standby (standby) and activated analog reserve way.
Four function keys to choose of pre-programmed music transfers or activating a transfers of a receipt on pre-programmed areas. 8 Channel keys to the switching on and off individual channels, optionally umprogrammierbar on activation a transfers of a receipt on pre-programmed areas. Volume control for each channel, which is bridged for emergency-related transfers. Access to all the controls can be locked. Built-in monitor speakers with volume control to listen to each channel.  Two ports for the monitoring of the emergency power supply. Separate, Goldfinger analogue input of the emergency. 6 Can be freely selectable filter per channel (parametric equalizer, high and low-pass, all pass, CD-Horn equalizer, treble / bass control, notch filters), delay (delay) to 682 ms and compressor. Compliant monitoring of all alarm-relevant signaling pathways, CPU, power supply and network connections. Optional connection of a 20 kHz pilot tone on each individual audio output.